Description
Fluke 1587 FC Offers
PI/DAR timed ratio tests (1587 FC only)
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
VFD low-pass filter for accurate motor drive measurements (1587?FC only)
Auto-discharge of capacitive voltage for added user protection
Insulation test (1587 FC: 0.01 M? to 2 G?) (1577: 0.1 M? to 600?M?)
Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V),(1577: 500 V, 1000 V) for many applications
AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (?), Continuity
Capacitance, diode test, temperature, Min/Max, frequency (Hz)(1587 FC only)
Auto power off to save battery power
CAT III 1000 V, CAT IV 600 V measurement category
Rugged, utility hard case allows you to bring everything you need for the job
Large display with backlight
Specifications:
Voltage DC
Maximum Voltage: 1000V
Maximum Resolution: 0.001V
Accuracy: ?(0.09%+2)
Voltage AC
Maximum Voltage: 1000V
Maximum Resolution: 0.1 mV
Accuracy: ?(2%+3)
Current DC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ?(0.2%+2)
Current AC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ?(1.5%+2)*
Resistance
Maximum Resistance: 50 M?
Maximum Resolution: 0.1?
Accuracy: ?(0.9%+2)
Insulation Test
Minimum Test Current @ 1k?/V:1mA
Test Voltages: 1577:500, 1000V
Maximum Resistance per Test Voltage: 50V; 100V; 250V; 500V; 1000V: 600 M?
Maximum Resolution per Test Voltage: 50V: 0.01 M?; 100V: 0.01 M?; 250V: 0.1 M?; 500V: 0.1 M?; 1000V: 0.1 M?
Accuracy per Test Voltage: 50V: ?(3% + 5); 100V: ?(3% + 5); 250V: ?(1.5% + 5)
General Specifications
Dimensions: 203x100x50mm (with holster)
Weight: 624g
Battery Life: Meter use: 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M? with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating: IP40
Specifications
Voltage DC Maximum Voltage 1000 V Accuracy ?(0.2%+2) Maximum Resolution 0.001V Voltage AC Maximum Voltage 1000 V Accuracy ?(2%+3) Maximum Resolution 0.1 mV Current DC Maximum Amps 400mA Amps Accuracy ?(1.0%+2) Maximum Resolution 0.01 mA Current AC Maximum Amps 400mA Amps Accuracy ?(2.0%+2) 1kHz bandwidth Maximum Resolution 0.01 mA Resistance Maximum Resistance 50 M? Accuracy ?(1.2%+2) Maximum Resolution 0.1? Insulation Test Minimum Test Current @ 1k?/V 1mA Test Voltages 500, 1000 V Maximum Resistance per Test Voltage 100V: 600 M? Maximum Resolution per Test Voltage 50V: 0.01 M?
100V: 0.01 M?
250V: 0.1 M?
500V: 0.1 M?
100V: 0.1 M? Accuracy per Test Voltage 50V: ?(3 % + 5)
100V: ?(3 % + 5)
250V: ?(1.5 % + 5)
500V: ?(2.0 % + 5)
100V: ?(2.0 % + 5) Environmental Specifications Operating temperature ?20 ?C to +55 ?C Storage temperature -40?C to +60?C Humidity (Without Condensation) 0% – 95% (10 ?C ? 30 ?C)
0% – 75% (30 ?C ? 40 ?C)
0% – 40% (40 ?C ? 55 ?C) Operating Altitude 2000 m Safety Specifications Overvoltage category Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V Agency Approvals 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V Mechanical & General Specifications Size 203 x 100 x 50 mm (with holster) Weight 624 g Warranty 3 years Battery life Alkaline Meter use 1000 hours Insulation test use Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M? with a duty cycle of 5 seconds on and 25 seconds off. IP Rating IP40