Description
The Fluke 1577 Insulation Multimeter combines a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
Like other tools that you have come to expect from Fluke, the 1577 is rugged, reliable, and easy to use.
Whether you work on motors, generators, cables, or switch-gear, the Fluke 1577 Insulation Multimeter is ideally suited to help you with your tasks.
What’s Included
Remote probe
Test leads
Alligator clips
Hard case
User documentation
Fluke 1577 Specifications
Voltage DC Maximum Voltage 1000 V Accuracy ?(0.2%+2) Maximum Resolution 0.001V Voltage AC Maximum Voltage 1000 V Accuracy ?(2%+3) Maximum Resolution 0.1 mV Current DC Maximum Amps 400mA Amps Accuracy ?(1.0%+2) Maximum Resolution 0.01 mA Current AC Maximum Amps 400mA Amps Accuracy ?(2.0%+2) 1kHz bandwidth Maximum Resolution 0.01 mA Resistance Maximum Resistance 50 M? Accuracy ?(1.2%+2) Maximum Resolution 0.1? Insulation Test Minimum Test Current @ 1k?/V 1mA Test Voltages 500, 1000 V Maximum Resistance per Test Voltage 100V: 600 M? Maximum Resolution per Test Voltage 50V: 0.01 M?
100V: 0.01 M?
250V: 0.1 M?
500V: 0.1 M?
100V: 0.1 M? Accuracy per Test Voltage 50V: ?(3 % + 5)
100V: ?(3 % + 5)
250V: ?(1.5 % + 5)
500V: ?(2.0 % + 5)
100V: ?(2.0 % + 5) Environmental Specifications Operating temperature ?20 ?C to +55 ?C Storage temperature -40?C to +60?C Humidity (Without Condensation) 0% – 95% (10 ?C ? 30 ?C)
0% – 75% (30 ?C ? 40 ?C)
0% – 40% (40 ?C ? 55 ?C) Operating Altitude 2000 m Safety Specifications Overvoltage category Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V Agency Approvals 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V Mechanical & General Specifications Size 203 x 100 x 50 mm (with holster) Weight 624 g Warranty 3 years Battery life Alkaline Meter use 1000 hours Insulation test use Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M? with a duty cycle of 5 seconds on and 25 seconds off. IP Rating IP40
Click here for complete specifications on the Fluke 1577
Reviews
There are no reviews yet.