Description
Fluke 1555 Insulation Resistance Tester, 10kV
Insulation resistance tester to 10,000V or 10kV makes this megohmmeter ideal for testing a wide range of high voltage equipment including switch gear, motors, generators and cables.
$5,199.99 Availability:
3 to 4 Weeks
Add to Cart
Fluke 1555/KIT Insulation Resistance Tester Kit, 10kV
Voltage breakdown detection alerts the user that voltage is present and gives the voltage reading up to 600V AC or DC for increased user safety. With selectable test voltages in 50V steps from 250 to 1000V and 100V steps above 1000V. Complete kit including test cable set.
$5,699.99 Availability:
2 to 3 Weeks
Add to Cart
Specifications
Insulation Resistance
Test voltage (DC) Range (DC) Accuracy (? reading)
250 V < 250 k? 250 k? to 5 G? 5 G? to 50 G? > 50 G?
Unspecified
5%
20%
Unspecified
500 V < 500 k? 500 k? to 10 G? 10 G? to 100 G? > 100 G?
Unspecified
5%
20%
Unspecified
1000 V < 1 M? 1 M? to 20 G? 20 G? to 200 G? > 200 G?
Unspecified
5%
20%
Unspecified
2500 V < 2.5 M? 2.5 M? to 50 G? 50 G? to 500 G? > 500 G?
Unspecified
5%
20%
Unspecified
5000 V < 5 M? 5 M? to 100 G? 100 G? to 1 T? > 1 T?
Unspecified
5%
20%
Unspecified
10000 V < 10 M? 10 M? to 200 G? 10 G? to 2 T? > 2 T?
Unspecified
5%
20%
Unspecified
Leakage Current Measurement
Range
1 nA to 2 mA
Accuracy
? (5 % + 2 nA)
Capacitance Measurement
Range
0.01 uF to 15.00?F
Accuracy
? (15 % rdg + 0.03?F)
Timer
Range
0 to 99 minutes
Accuracy
Resolution Setting: 1 minute Indication: 1 second
Live Circuit Warning
Range
Warning Range 30 V to 660 V AC/DC, 50/60 Hz
Accuracy
Voltage Accuracy ? (15 % + 2 V)
Additional
Bar Graph Range
0 to 1 T?
Insulation Test Voltage Accuracy
-0 %, +10 % at 1 mA load current
Induced AC Mains Current Rejection
2 mA maximum
Charging Rate for Capacitive Load
5 seconds per ?F
Discharge Rate for Capacitive Load
1.5 s/?F
Click here for complete specifications on the Fluke 1555