Description
Fluke 1503 Offers
Ideal for many preventative maintenance, commissioning, and troubleshooting applications.
Features
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
Auto-discharge of capacitive voltage for added user protection
Save battery power with auto power off
Read measurements easily with large, backlit display
CAT IV 600 V overvoltage category rating for added user protection
Remote probe, test leads, probes and alligator clips included with each tester
Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
Applications
Preventive Maintenance
Fluke 1503 Specifications
AC/DC Voltage Specifications
Range
600.0V
Resolution
0.1V
Accuracy
50 Hz to 400 Hz: ?(2% of rdg + 3 digits)
Input Impedance
3M? (nominal), < 100pF Common Mode Rejection Ratio (1k? unbalanced) > 60dB at DC, 50 or 60Hz
Overload Protection
600V RMS or DC
Earth Bond Resistance Specifications
Range
20.00? to 20.00k?
Resolution
0.01? to 0.01k?
Accuracy
?(1.5% + 3 digits)
Overload Protection
2V RMS or DC
Open Circuit Test Voltage
> 4.0V, < 8V Short Circuit Current > 200.0mA
Insulation Specifications
Output Voltages
500 to 1000V (0 to 20%)
Test Currents
1mA at 500k? to 1M?
Measurement Range
0.01M? to 2000M?
Test Voltages
50V, 100V, 250V, 500V, 1000V
Test Voltage Accuracy
+20%, -0%
Short-Circuit Test Current
1mA nominal
Auto Discharge
Discharge time < 0.5 second for C = 1?F or less Live Circuit Detection Inhibit test if terminal voltage > 30V prior to initialization of test
Maximum Capacitive Load
Operable with up to 1?F load
Click here for complete specifications on the Fluke 1503
Reviews
There are no reviews yet.