Fluke 710 Offers
Features
Key valve testing functions – valve signature test, speed test, step test, manual test, bump/partial stroke test
Key mA loop calibrator functions – mA source, mA simulate, mA read, mA read/loop power, and volts read
ValveTrack? software – enables upload to a PC for further in-depth analysis of valve measurements that are logged and recorded to memory
Valve test procedures that deliver Good, Marginal or Bad assessment of a control valve
Generic HART communication
Best-in-class mA accuracy at 0.01% measurement or source value
Compact rugged design
Intuitive user interface with Quick-Set knob for fast setup, easy to use
24 V DC loop power with mA measure mode (-25 to 125%)
Resolution of 1 ?A on mA ranges and 1 mV on voltages ranges
Built in selectable 250 ? resistor for HART communications
Simple two wire connection for all measurements
Auto shutdown to conserve battery life
Variable step and ramp time in seconds
Offers a built-in HART modem to communicate the following HART commands:
Read sensor PV information
Read PV output information
Read and write PV unit type, tag ID name, descriptor, and message
Read and write PV ranges (upper and lower)
Enter/exit fixed current mode
Set zero offset
Trim DAC zero (mA output 4 mA)
Trim DAC gain (mA output 20 mA)
Smart Control Valve Testing is Now Easier Than Ever
The valve testing loop calibrator is designed to enable users to perform quick, easy tests on HART smart control valves. Featuring built-in test procedures and an intuitive user interface, it allows users to quickly and easily perform valve tests, while the valve test quick-check results provide at-a-glance diagnostics help you make maintenance decisions faster than ever. The valve health quick-check results let you know whether your valve is in good, marginal or in bad operating condition so you can quickly decide whether additional maintenance is necessary.
Valve Testing and HART Communication in a Precision Loop Calibrator
With the valve testing loop calibrator?s built in HART communication function, users can source a 4-20 mA signal to cause the smart control valve to move, while simultaneously interpreting the valve?s HART feedback signal to determine whether the valve is moving to the expected position. In addition to positional information, the measured pressure delivered from the valve?s internal I/P (which moves the valve) can be determined through the HART communication protocol. It has built-in test procedures that automatically increase and change the mA signal while monitoring the HART position and pressure feedback from the control valve, giving you a better overall picture of valve health at the simple push of a button.
Pre-Configured Valve Tests, At-A-Glance Answers
Valve test routines built into it include:
Manual testing: manually change the mA signal and view the HART position and pressure variable information
Full range ramping of the mA signal from 4 to 20 to 4 mA while recording the 0-100-0% position, or the pressures applied that move the valve from 0-100-0%
Stepping the mA signal on the input to the valve in steps and evaluating the valves response to the mA input changes
Speed tests to determine how fast the valve can open or close
Bump and partial stroke tests that help test valves over a portion of their range so they can be tested in a live process
ValveTrack? Software Enables Further Analysis and Trending
Valve tests that are logged and recorded to memory in the loop valve tester are available to upload to included ValveTrack? analysis software.
ValveTrack? software enables you to:
Upload, print and plot logged valve tests taken in the field
Compare previous uploaded tests to recent tests
View valve test history by HART Tag ID
Export valve test data to CSV for additional analysis in Microsoft Excel?
Saving Time, Getting Answers
In addition, it offers:
Logging of HART data in the field – once recorded by the loop valve tester in the field, the ValveTrack? software can upload the HART configuration of up to (20) HART devices in your plant and output data in either (.csv) or (.txt) format
Data logged mA loop measurements and HART data can be recorded from a particular transmitter for troubleshooting and loop tuning
The data log feature offers selectable capture with recording intervals of 1 to 60 seconds and a logging capacity of 9800 records or 99 individual sessions – each record contains the mA measurement and all four process variables
Applications
Oil and gas
Food and beverage
Waste/wastewater
Pharmaceuticals
Process automation
Fluke 710 Specifications
Functions
mA source, mA simulate, mA read, mA read/loop power, and volts read
Ranges
mA (0 to 24 mA) and Volts (0 to 30 V dc)
Resolution
1uA on mA ranges and 1mV on voltage range
Accuracy
0.01% ?2 counts all ranges (@ 73.4?F ?41?F [23?C ?5?C])
Operating Temperature Range
14 to 131?F (-10 to 55?C)
Humidity Range
10 to 95% non-condensing
Stability
20 ppm of F.S./?C from -10 to 18?C and 28 to 55?C
Display
128 x 64 pixels, LCD graphic w/backlight, .34 in high digits
Power
6 x AAA alkaline
Battery Life
?40 hours continuous use (measure mode using alkaline)
Loop Compliance Voltage
24 V dc @ 20 mA
Voltage Protection
240 V ac
Overload Current Protection
28 mA dc
EMC
EN61326 Annex A (portable instruments)
Dimensions
6 x 3.6 x 1.3″ (15 x 9 x 3 cm)
Weight
0.3 kg (9.5 oz)
Warranty
Three year